Technical Summary
| Product type designation | AI Energy Meter RC ST |
|---|---|
| Supply voltage, rated value (DC) | 24 V |
| Current consumption (rated value) | 12.5 mA |
| Current consumption, max. | 17 mA |
| Power loss, typ. | 400 mW; 3x 230 V AC |
| Usable BaseUnits | BU type U0 |
| Measuring procedure for voltage measurement | TRMS |
| Measuring procedure for current measurement | TRMS |
| Measurable line voltage between phase and neutral conductor | 277 V |
| Measurable line voltage between the line conductors | 480 V |
| STEP 7 TIA Portal configurable/integrated from version | STEP 7 V16 or higher with HSP |
Key Features
Product type designation for this SIMATIC ET 200SP analog input module.
Supports energy, frequency, power, active power, reactive power, power factor, and active factor measurement.
Suitable for Rogowski coils and current-voltage-converter inputs with a 333 mV interface.
Designed for use with BU type U0.
Includes channel diagnostics and I&M data from I&M0 to I&M3.
Applications
Measures energy, frequency, power, active power, reactive power, and power factor.
Supports voltage measurement and current measurement, including use with Rogowski coils and current-voltage-converter inputs.
Provides cyclic and acyclic measured value access for measured and calculated values.
Frequently Asked Questions
What is 6ES7134-6PA21-0BU0 in SIMATIC ET 200SP?
It is an analog input module with the AI Energy Meter RC ST product type designation.
Which measurement functions does AI Energy Meter RC ST support?
It supports voltage, current, energy, frequency, power, active power, reactive power, power factor, and active factor measurement.
What supply voltage does 6ES7134-6PA21-0BU0 use?
Rated value (DC): 24 V. Permissible range: 19.2 V to 28.8 V.
Which base unit and mounting position apply to this module?
Usable BaseUnits: BU type U0. Mounting position: any.
Which engineering versions are listed for this module?
STEP 7 TIA Portal configurable/integrated from STEP 7 V16 or higher with HSP. STEP 7 configurable/integrated via GSD file. PROFIBUS from GSD revision 3 and 5 and higher. PROFINET from GSD version/revision V2.3.