Technical Summary
| Product type designation | AQ 2xU/I ST |
|---|---|
| Firmware version | V1.0.0 |
| Firmware update possible | Yes |
| Number of analog outputs | 2 |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Supply voltage, rated value (DC) | 24 V |
| Supply voltage, permissible range | 19.2 V to 28.8 V |
| Current consumption, max. | 110 mA |
| Power consumption from the backplane bus | 0.65 W |
| Power loss, typ. | 2.7 W |
| Cycle time (all channels), min. | 3.2 ms; independent of number of activated channels |
| Output ranges, voltage | 0 to 10 V; 1 V to 5 V; -10 V to +10 V |
| Output ranges, current | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Potential separation between channels and backplane bus | Yes |
| Potential separation between channels and load voltage L+ | Yes |
Key Features
SIMATIC S7-1500 analog output module AQ 2xU/I ST.
2 channels in groups of 2.
Resolution with overrange (bit including sign), max.: 16 bit.
Accuracy: 0.3%.
Diagnostics function: Yes. Substitute values connectable: Yes.
Supports safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015.
Applications
Provides voltage or current output signals to connected actuators.
Supports the safety-oriented shutdown of load groups up to SIL2 and Category 2 / PL c.
Frequently Asked Questions
What is 6ES7532-5NB00-0AB0 in the SIMATIC S7-1500 range?
It is an SIMATIC S7-1500 analog output module with product type designation AQ 2xU/I ST.
How many analog outputs does this module have?
It has 2 analog outputs in groups of 2.
What supply voltage does 6ES7532-5NB00-0AB0 require?
Rated value (DC): 24 V. Permissible range: 19.2 V to 28.8 V.
What output signal ranges are supported?
Voltage outputs: 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current outputs: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
What installation or connection details are provided for this module?
Delivery includes front connector push-in, infeed element, shielding bracket, and shield terminal. The shielded cable length is up to 800 m.