Technical Summary
| Product type designation | CPU 416-5H PN/DP |
|---|---|
| Hardware functional status | 1 |
| Firmware version | V6.0 |
| Work memory | 16 Mbyte |
| Work memory for program | 6 Mbyte |
| Work memory for data | 10 Mbyte |
| Load memory expandable FEPROM | Yes; with Memory Card (FLASH) |
| Rated value (DC) | Power supply via system power supply |
| Input current from backplane bus 5 V DC, typ. | 1.6 A |
| Power loss, typ. | 7.5 W |
| Interface type | MPI/PROFIBUS DP |
| Number of interfaces | 5 |
| Number of ports | 2 |
| Transmission rate, max. | 100 Mbit/s |
| PROFINET IO Controller | Yes |
Key Features
CPU 416-5H PN/DP central processing unit for S7-400H and S7-400F/FH.
1x MPI/DP, 1x DP, 1x PN and 2 for sync modules.
16 MB memory with 10 MB data and 6 MB program.
PROFINET IO Controller with 2 RJ 45 (Ethernet) ports and integrated switch.
PROFIBUS DP master interface with up to 12 Mbit/s transmission rate.
Applications
Central processing for S7-400H and S7-400F/FH control tasks.
Connection and control of PROFINET IO devices through the integrated PROFINET interface.
Integration of PROFIBUS DP networks through the DP interface.
Frequently Asked Questions
What is the exact product type of 6ES7416-5HS06-0AB0?
It is a CPU 416-5H PN/DP central processing unit.
How much memory does this CPU have?
It has 16 MB memory, made up of 10 MB data and 6 MB program.
Which interfaces are included on 6ES7416-5HS06-0AB0?
It includes 1x MPI/DP, 1x DP, 1x PN, and 2 interfaces for sync modules.
What are the PROFINET connection details?
The integrated PROFINET interface is a PROFINET IO Controller with 2 RJ 45 (Ethernet) ports and an integrated switch.
What is the maximum PROFIBUS DP transmission rate?
The PROFIBUS DP interface supports up to 12 Mbit/s.