Technical Summary
| Product type designation | AI 4xRTD/TC 2-/3-/4-wire HF |
|---|---|
| Based on | 6ES7134-6JD00-0CA1 |
| Usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC00 |
| Number of analog inputs | 4 |
| Resolution | 16 bit |
| Accuracy | +/-0.2% |
| Rated value (DC) | 24 V |
| Current consumption (rated value) | 30 mA |
| Power loss, typ. | 0.75 W |
| Ambient temperature during operation, horizontal installation | -40 °C; = Tmin (incl. condensation/frost) |
| Ambient temperature during operation, horizontal installation max. | 60 °C; = Tmax; +70 °C for 10 min (OT2, ST1/ST2 acc. to EN 50155) |
Key Features
Analog input module with 4 channels.
Product type designation: AI 4xRTD/TC 2-/3-/4-wire HF.
Conformal coating for the printed circuit board assemblies.
Channel diagnostics are supported.
16 bit signal resolution.
Accuracy: +/-0.2%.
Applications
For measuring RTD and thermocouple signals on 4 analog inputs.
For connection of resistance measurement with 2-wire, 3-wire, or 4-wire wiring.
Frequently Asked Questions
What is Siemens 6AG2134-6JD00-1CA1?
It is a SIPLUS ET 200SP AI 4xRTD/TC HF rail analog input module.
How many analog inputs does 6AG2134-6JD00-1CA1 have?
It has 4 analog inputs.
What wiring does the AI 4xRTD/TC HF module support?
It supports 2-wire, 3-wire, and 4-wire connection for resistance measurement.
What are the supply requirements for 6AG2134-6JD00-1CA1?
Rated value (DC): 24 V. Permissible range: 19.2 V to 28.8 V.
What is the operating temperature range for this SIPLUS ET 200SP module?
Horizontal installation is rated from -40 °C to 60 °C, with +70 °C for 10 minutes under OT2, ST1/ST2 conditions.