Technical Summary
| Product type | SINAMICS Power Module PM240-2 |
|---|---|
| Status | spare part |
| Integrated filter | integrated Class A filter |
| Braking chopper | integrated braking chopper |
| Supply voltage | 380-480 V 3 AC +10/-10% |
| Supply frequency | 47-63 Hz |
| Power high overload | 2.2kW at 200% 3 s, 150% 57 s, 100% 240 s |
| Power low overload | 3 kW at 150% 3 s, 110% 57 s, 100% 240 s |
| Ambient temperature high overload | -10 to +50 °C |
| Ambient temperature low overload | -10 to +40 °C |
| Degree of protection | IP20-PT |
| Release status | released as of CU firmware version V4.6 |
| Control Unit and operation panel | without Control Unit and operation panel |
Key Features
Power Module PM240-2 for the SINAMICS range.
Includes an integrated Class A filter.
Includes an integrated braking chopper.
2.2kW at 200% 3 s, 150% 57 s, 100% 240 s; ambient temperature -10 to +50 °C.
3 kW at 150% 3 s, 110% 57 s, 100% 240 s; ambient temperature -10 to +40 °C.
IP20-PT without Control Unit and operation panel.
Frequently Asked Questions
What is Siemens 6SL3211-1PE18-0AL1?
It is a SINAMICS Power Module PM240-2 spare part.
What input rating does 6SL3211-1PE18-0AL1 use?
380-480 V 3 AC +10/-10% at 47-63 Hz.
What are the overload ratings for 6SL3211-1PE18-0AL1?
High overload: 2.2kW at 200% 3 s, 150% 57 s, 100% 240 s. Low overload: 3 kW at 150% 3 s, 110% 57 s, 100% 240 s.
What protection and configuration details are listed for 6SL3211-1PE18-0AL1?
It has IP20-PT protection and is supplied without Control Unit and operation panel.
What are the dimensions of 6SL3211-1PE18-0AL1?
238x 126x 171 (HxWxD).