Technical Summary
| Product type designation | CM 1241 RS 232 |
|---|---|
| Based on | 6ES7241-1AH32-0XB0 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 200 mA; From backplane bus 5 V DC |
| Power loss, typ. | 1.1 W |
| Interfaces/bus type | RS 232C (V.24) |
| Number of interfaces | 1 |
| Ambient temperature during operation, min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C |
| Ambient temperature during operation, max. | 70 °C; = Tmax |
| IP degree of protection | IP20 |
Key Features
Communications module for the S7-1200 family with Product type designation CM 1241 RS 232.
Includes 1 interface with Interfaces/bus type RS 232C (V.24).
Supports Freeport.
Built with conformal coating for high reliability.
Uses a 9-pole D-sub (pin) interface connection.
Applications
For point-to-point connection over RS 232C (V.24) with a cable length up to 10 m.
For Modbus RTU master and Modbus RTU device communication.
For Freeport communication with telegram lengths up to 1 kbyte.
Frequently Asked Questions
What is Siemens 6AG1241-1AH32-2XB0?
It is a SIPLUS S7-1200 CM 1241 RS-232 communications module.
Which interface does 6AG1241-1AH32-2XB0 use?
It uses 1 RS 232C (V.24) interface.
What communication functions are supported by 6AG1241-1AH32-2XB0?
It supports Freeport, ASCII, Modbus RTU master, and Modbus RTU device.
What are the electrical supply values for 6AG1241-1AH32-2XB0?
Rated value (DC) is 24 V, with a permissible range of 20.4 V to 28.8 V.
What are the operating temperature limits of 6AG1241-1AH32-2XB0?
The operating range is -40 °C to 70 °C, with start-up at -25 °C.